Description: The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 3rd value pair of the characteristic.
Sets the third flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency: The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0368
Note: For induction motors, p0364 = 100 % corresponds to the rated motor flux.
For separately-excited synchronous motors p0364 = 100% corresponds to an induced terminal voltage with the
magnitude of the rated motor voltage (under no-load conditions at the synchronous speed).
Description: The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 4th value pair of the characteristic.
Sets the fourth flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency: The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0369
Note: For induction motors, p0365 = 100 % corresponds to the rated motor flux.
For separately-excited synchronous motors p0365 = 100% corresponds to an induced terminal voltage with the
magnitude of the rated motor voltage (under no-load conditions at the synchronous speed).
Description: The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the x coordinate (magnetizing current) for the 1st value pair of the characteristic.
Sets the first magnetizing current of the saturation characteristic as a [%] referred to the rated magnetizing current
(r0331), for separately-excited synchronous motors referred to the no-load excitation current.
Dependency: The following applies for the magnetizing currents:
p0366 < p0367 < p0368 < p0369
Refer to: p0362
p0364[0...n] Saturation characteristic flux 3 / Mot saturat.flux 3
VECTOR Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: PEM Expert list: 1
Min Max Factory setting
10.0 [%] 300.0 [%] 115.0 [%]
p0365[0...n] Saturation characteristic flux 4 / Mot saturat.flux 4
VECTOR Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: PEM Expert list: 1
Min Max Factory setting
10.0 [%] 300.0 [%] 125.0 [%]
p0366[0...n] Saturation characteristic I_mag 1 / Mot sat. I_mag 1
VECTOR Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: PEM Expert list: 1
Min Max Factory setting
5.0 [%] 800.0 [%] 50.0 [%]