F35011 TM54F: Drive object number assignment illegal
Drive object: A_INF, B_INF, CU_LINK, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41, TM54F_MA,
TM54F_SL, VECTOR
Reaction: NONE
Acknowledge: IMMEDIATELY (POWER ON)
Cause: A drive object number was assigned twice. Each drive object number can be assigned only once.
Remedy: Correct the assignment of the drive object numbers.
See also: p10010 (SI drive object assignment)
A35012 TM54F: Test stop active
Drive object: A_INF, B_INF, CU_LINK, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41, TM54F_MA,
TM54F_SL, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The test stop for the Terminal Module 54F (TM54F) is presently being executed.
F35013 is output when a error occurs during the test stop.
Remedy: The alarm disappears automatically after successfully ending or canceling (when a fault condition occurs) the test
stop.
F35013 TM54F: Test stop error
Drive object: A_INF, B_INF, CU_LINK, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41, TM54F_MA,
TM54F_SL, VECTOR
Reaction: NONE
Acknowledge: IMMEDIATELY (POWER ON)
Cause: An error was detected when carrying out the test stop on the TM54F. As fault response, instead of the fail-safe input
image, a logical 0 signal is transferred to the motion monitoring function.
Fault value (r0949, interpret hexadecimal):
0xaaaabbcc hex
aaaa: Specifies the DOs or F-DIs (dependent on test step cc) for which the expected state was not assumed. The
number is bit-coded (bit 0 = F-DI 0 or F-DO 0; bit 3 = F-DI 3 or F-DO 3).
bb: Precise problem:
0x01 = Internal error (error state on the opposite side).
0x02 = Error when comparing the switching signals.
0x03 = Internal error (delay time in the new state has still not expired).
cc: Test step of the test stop in which the error has occurred.
Test stop step cc for slave (hexadecimal):
0x00: Action: L1+ switched-out, L2+ switched-in - error: Master not in initial state 0x00 and 0x0A.
0x0A: Action: L1+ switched-out, L2+ switched-in - error: Master not in state 0x15.
0x15: Action: L1+ switched-out, L2+ switched-out - error: F-DIs 0...4 of the master do not correspond to those of the
slave (expected: level 0) or master not in state 0x20.
0x20: Action: L1+ switched-out, L2+ switched-out - error: Master not in state 0x2B.
0x2B: Action: L1+ switched-in, L2+ switched-in - error: F-DIs 5...9 of the master do not correspond to those of the
slave (expected: level 0) or master not in state 0x36.
0x36: Action: All slave DOs at OFF - error: Master not in state 0x41.
0x41: Action: All slave DOs at OFF - error: Master not in state 0x4C.
0x4C: Action: All slave-DOs at ON - error: State of DI 20...23 does not correspond to the expected state (24V) or the
master not in state 0x57.
0x57: Action: All slave DOs at ON - error: Master not in state 0x62.
0x62: Action: All slave-DOs at OFF - error: State of DI 20...23 does not correspond to the expected state (0V) or the
master not in state 0x6D.
0x6D: Action: All slave DOs at OFF - error: Master not in state 0x78.
0x78: Action: All slave-DOs at ON - error: State of DI 20...23 does not correspond to the expected state (0V) or the
master not in state 0x83.
0x83: Action: All slave DOs at ON - error: Master not in state 0x8E.
0x8E: Action: All slave-DOs at OFF - error: State of DI 20...23 does not correspond to the expected state (0V) or the
master not in state 0x99.
0x99: Action: All slave DOs at OFF - error: Master not in state 0xA4.
0xA4: Action: All slave-DOs at OFF - error: State of DI 20...23 do not correspond to the expected state 24V) or the
master not in state 0xAF.
0xAF: Action: All slave DOs at the original state - error: Master not in state 0xBA.