Parameters
List of parameters
1-196
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: Refer to: p0488, p0489, p0495, p0728
Notice: To the terminal designation:
The second designation is only applicable for CU310.
Note: The terminal must be set as input.
When the measuring probe or the equivalent zero mark is inverted, this has no effect on the status displays of the
digital inputs (r0721, r0722, r0723).
DI: Digital input, DO: Digital output
Description: Setting to invert the digital input signals to connect a measuring probe or an equivalent zero mark.
Notice: To the terminal designation:
The second designation is only applicable for CU310.
Note: The terminal must be set as input.
When the measuring probe or the equivalent zero mark is inverted, this has no effect on the status displays of the
digital inputs (r0721, r0722, r0723).
DI: Digital input, DO: Digital output
Description: Sets the behavior for the ENCODER fault response (motor encoder).
This means, for example, if an encoder fault occurs, sensorless operation can be automatically selected with a
shutdown behavior that can be selected.
Values: 0: Encoder fault results in OFF2
1: Enc fault results in sensorless oper. and oper. continues
2: Encoder fault results in sensorless operation and OFF1
3: Encoder fault results in sensorless operation and OFF3
4: Encoder fault results in an int. armature short-cct. / DC brake
Dependency: The following parameters are relevant for sensorless operation.
Refer to: p0341, p0342, p1470, p1472, p1517, p1612, p1755
Refer to: F07575
Bit field: Bit Signal name 1 signal 0 signal FP
09 DI/DO 9 (X122.8/X121.8) Inverted Not inverted -
10 DI/DO 10 (X122.10/X121.10) Inverted Not inverted -
11 DI/DO 11 (X122.11/X121.11) Inverted Not inverted -
13 DI/DO 13 (X132.8) Inverted Not inverted -
14 DI/DO 14 (X132.10) Inverted Not inverted -
15 DI/DO 15 (X132.11) Inverted Not inverted -
p0490 Invert measuring probe or equivalent zero mark / Meas. probe invert
CU_CX32 Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
09 DI/DO 9 (X122.8/X121.8) Inverted Not inverted -
10 DI/DO 10 (X122.10/X121.10) Inverted Not inverted -
11 DI/DO 11 (X122.11/X121.11) Inverted Not inverted -
13 DI/DO 13 (X132.8) Inverted Not inverted -
14 DI/DO 14 (X132.10) Inverted Not inverted -
15 DI/DO 15 (X132.11) Inverted Not inverted -
p0491 Motor encoder fault response ENCODER / Fault resp ENCODER
SERVO Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 4 0