Parameters
Overview of parameters
1-20
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Data type
The information on the data type can consist of the following two pieces of infor-
mation (separated by a slash):
First information
Data type of the parameter
Second information (only for binector or connector input)
Data type of the signal source to be interconnected (binector/connector
output).
The possible data types of parameters are as follows:
Depending on the data type of the BICO input parameter (signal sink) and BICO
output parameter (signal source) the following combinations are possible when
creating BICO interconnections:
I8 Integer8 8-bit integer
I16 Integer16 16-bit integer
I32 Integer32 32-bit integer
U8 Unsigned8 8 bits without sign
U16 Unsigned16 16 bits without sign
U32 Unsigned32 32 bits without sign
Float FloatingPoint32 32-bit floating point number
Table 1-2 Possible combinations of BICO interconnections
BICO input parameter
CI parameter BI parameter
BICO output parameter Unsigned32 /
Integer16
Unsigned32 /
Integer32
Unsigned32 /
FloatingPoint32
Unsigned32 /
Binary
CO: Unsigned8 x x
CO: Unsigned16 x x
CO: Integer16 x x
CO: Unsigned32 x x
CO: Integer32 x x
CO: FloatingPoint32 x x x
1
BO: Unsigned8 x
BO: Unsigned16 x
BO: Integer16 x
BO: Unsigned32 x

Table of Contents