List of parameters
Parameters
1-33
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
120: [120] Module de-activated
250: [250] Device signals a topology error
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
Description: Operating display for Terminal Module 41 (TM41).
Values: 0: [00] Operation - everything enabled
10: [10] Operation - set "enable setpoint" = "1" (p1142)
12: [12] Operation - RFG frozen, set "RFG start" = "1" (p1141)
13: [13] Operation - set "enable RFG" = "1" (p1140)
18: [18] Operation - brake on fault remove fault acknowledge
21: [21] Ready - set "enable operation" = "1" (p0852)
31: [31] Ready to power-up - set "ON/OFF1" = "0/1" (p0840)
41: [41] Power-on inhibit - set "ON/OFF1" = "1/0" (p0840)
42: [42] Power-on inhibit - set "OC/OFF2" = "1" (p0844)
43: [43] Power-on inhibit - set "OC/OFF3" = "1" (p0848)
45: [45] Power-on inhib - remove fault cause, acknowledge fault
46: [46] Power-on inhibit - exit comm mode (p0009, p0010)
120: [120] Module de-activated
250: [250] Device signals a topology error
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
Note: OC: Operating condition
RFG: Ramp-function generator
COMM: Commissioning
Description: Operating display for Terminal Module 17 (TM17).
Values: 0: [00] Module in cyclic operation
40: [40] Module not in cyclic operation
50: [50] Alarm
60: [60] Fault
70: [70] Initialization
120: [120] Module de-activated
250: [250] Device signals a topology error
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
r0002 TM41 operating display / TM41 op_display
TM41 Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 250 -
r0002 TM17 operating display / TM17 op_display
TM17 Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 250 -