List of parameters
Parameters
1-333
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the status word for the ramp-function generator (RFG).
Note: Re bit 02:
The bit is an OR logic operation - bit 00 and bit 01.
Description: Sets the operating mode for flying restart.
The flying restart allows the drive converter to be powered-up while the motor is still rotating. In so doing, the drive
converter output frequency is changed until the actual motor speed/velocity is found.. The motor then accelerates
up to the setpoint at the ramp generator setting.
Values: 0: Flying restart inactive
1: Flying restart always active (start in setpoint direction)
2: FlyRestart active after on fault OFF2 (start in setp. dir.)
3: FlyRestart active after fault OFF2 (start in setp. direction)
4: Flying restart always active (start only in setpoint direction)
5: FlyRestart active after on fault OFF2 (start only in setp_dir)
6: FlyRestart active after fault OFF2 (start only in setp. dir.)
Dependency: A differentiation is made between flying restart for V/f control and for vector control (p1300).
Flying restart, V/f control: p1202, p1203, r1204
Flying restart for vector control: p1202, p1203, r1205
Notice: The "flying restart" function must be used in cases where the motor is possibly still running (e.g. after a brief line
supply interruption) or is being driven by the load. The system might otherwise shut down as a result of overcurrent.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fixed setpoint bit 0 Yes No -
01 Fixed setpoint bit 1 Yes No -
02 Fixed setpoint bit 2 Yes No -
03 Fixed setpoint bit 3 Yes No -
05 Inhibit negative direction Yes No -
06 Inhibit positive direction Yes No -
11 Direction reversal Yes No -
13 Motorized potentiometer raise Yes No -
14 Motorized potentiometer lower Yes No -
15 Bypass ramp-function generator Yes No -
r1199.0...6 CO/BO: Ramp-function generator status word / RFG ZSW
SERVO (Extended
setp), VECTOR
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 1550, 3080,
8010
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Ramp-up active Yes No -
01 Ramp-down active Yes No -
02 Ramp-function generator active Yes No -
03 Ramp-function generator set Yes No -
04 Ramp-function generator held Yes No -
05 Ramp-function generator tracking active Yes No -
06 Maximum limit active Yes No -
p1200[0...n] FlyRest oper mode / FlyRest op_mode
VECTOR Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: 1690
P-Group: Functions Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0 6 0