Parameters
List of parameters
1-336
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Modifies the pre-charging monitoring of the infeed.
The active automatic restart (AR) of the following drive object can be interconnected using this binector input (BI:
p1207 = r1214.2).
This means that when the automatic restart is operational, the pre-charging monitoring of the infeed is de-activated
and is only re-activated under the following conditions:
- the absolute current in the DC link is greater than 2 % of the maximum current (r0209) of the infeed to provide pro-
tection against short-circuit in the DC link.
- if a Voltage Sensing Module (VSM) is being used, the line supply voltage amplitude is greater than 3 % of the
parameterized unit supply voltage (p0210) to protect the pre-charging resistors against continuos filter current when
the line supply partially returns.
Dependency: Refer to: r0209, p0210, r1214
Description: Sets the signal source to modify the automatic restart (AR).
Interconnections between the automatic restart and infeed:
With the following interconnection in the mode p1210 = 6, the automatic restart can respond to infeed faults:
BI: p1208[0] = r2139.3
With the following interconnection, in the mode p1210 = 4, the automatic restart can respond to line supply failure of
the infeed:
BI: p1208[1] = r0863.2
Index: [0] = Infeed fault
[1] = Infeed line supply failure
Dependency: Refer to: r0863, r2139
Description: Sets the automatic restart mode (AR).
Values: 0: Disables automatic restart
1: Acknowledges all faults without restarting
4: Restart after power failure without additional start attempts
6: Restart after fault with additional start attempts
Dependency: The automatic restart requires an active ON command, e.g. that is available at a digital input.
If, for p1210 > 1, there is no active ON command, then the automatic restart is interrupted.
When using an Advanced Operator Panel (AOP) in the LOCAL Mode, then there is no automatic restart.
p1207 BI: AR connection following drive object / AR connection DO
A_INF, B_INF,
S_INF
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p1208[0...1] BI: AR modification infeed / AR modification
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p1210 Automatic restart, mode / AR mode
A_INF, B_INF,
S_INF
Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 6 0