List of parameters
Parameters
1-373
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the third point along the characteristic.
Dependency: The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard charac-
teristic is used that contains the rated motor operating point.
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1325, p1326, p1327
Description: The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the third point along the characteristic.
Dependency: Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1326, p1327
Description: In the servo control mode the following applies:
The linear characteristic for the V/f control is defined by 0 Hz / p1319 and p1326 / p1327.
For vector control, the following applies:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the fourth point along the characteristic.
Dependency: In the servo control mode the following applies:
Activates the V/f control using p1317.
For vector control, the following applies:
Selects the freely programmable characteristic using p1300 = 3.
The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard charac-
teristic is used that contains the rated motor operating point.
Refer to: p1310, p1311, p1317, p1319, p1320, p1321, p1322, p1323, p1324, p1325, p1327
Note: In the servo control mode the following applies:
Linear interpolation is carried out between the points 0 Hz / p1319 and p1326 / p1327.
For vector control, the following applies:
Linear interpolation is carried out between the points 0 Hz / p1310, p1320 / p1321 ... p1326 / p1327. For output fre-
quencies above p1326, the characteristic is extrapolated with the gradient between the characteristic points
p1324/p1325 and p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable V/Hz characteristic.
p1324[0...n] V/f control programmable characteristic frequency 3 / Uf char f3
VECTOR Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6300
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]
p1325[0...n] V/f control programmable characteristic voltage 3 / Uf char U3
VECTOR Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6300
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [Vrms] 10000.0 [Vrms] 0.0 [Vrms]
p1326[0...n] V/f control programmable characteristic frequency 4 / Uf char f4
SERVO, VECTOR Can be changed: U, T Calculated: CALC_MOD_REG Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5300, 6300
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 10000.00 [Hz] 0.00 [Hz]