Parameters
List of parameters
1-388
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the time constant for the speed setpoint filter 1 (PT1).
Dependency: Refer to: p1414, p1415
Note: For SERVO (p0107) the following applies:
This parameter is only effective if the speed filter is set as a PT1 low pass.
Description: Sets the time constant for the velocity setpoint filter 1 (PT1).
Dependency: Refer to: p1414, p1415
Note: This parameter is only effective if the velocity filter is set as a PT1 low pass.
Description: Sets the time constant for the speed setpoint filter 1 (PT1).
Note: For SERVO (p0107) the following applies:
This parameter is only effective if the speed filter is set as a PT1 low pass.
Description: Sets the denominator natural frequency for the speed setpoint filter 1 (PT2, general filter).
Dependency: Refer to: p1414, p1415
Note: This parameter is only effective if the speed filter is parameterized as a PT2 low pass or as general filter.
The filter is only effective if the natural frequency is less than half of the sampling frequency.
p1416[0...n] Speed setpoint filter 1 time constant / n_set_filt 1 T
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5020
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.00 [ms] 5000.00 [ms] 0.00 [ms]
p1416[0...n] Velocity setpoint filter 1 time constant / v_set_filt 1 T
SERVO (Lin) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5020
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.00 [ms] 5000.00 [ms] 0.00 [ms]
p1416[0...n] Speed setpoint filter 1 time constant / n_set_filt 1 T
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6030
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.00 [ms] 5000.00 [ms] 0.00 [ms]
p1417[0...n] Speed setpoint filter 1 denominator natural frequency / n_set_filt 1 fn_d
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5020
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.5 [Hz] 16000.0 [Hz] 2000.0 [Hz]