List of parameters
Parameters
1-391
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the numerator damping for velocity setpoint filter 1 (general filter).
Dependency: Refer to: p1414, p1415
Note: This parameter is only effective if the velocity filter is set as a general filter.
Description: Sets the type for speed setpoint filter 2.
Values: 0: Low pass: PT1
1: Low pass: PT2
2: General 2nd-order filter
Dependency: PT1 low pass: p1422
PT2 low pass: p1423, p1424
General filter: p1423 - p1426
Description: Sets the type for speed setpoint filter 2.
Values: 0: Low pass: PT1
1: Low pass: PT2
2: General 2nd-order filter
Dependency: PT1 low pass: p1422
PT2 low pass: p1423, p1424
General filter: p1423 - p1426
Description: Sets the time constant for the speed setpoint filter 2 (PT1).
Dependency: Refer to: p1414, p1421
Note: This parameter is only effective if the speed filter is set as a PT1 low pass.
p1420[0...n] Velocity setpoint filter 1 numerator damping / v_set_filt 1 D_n
SERVO (Lin) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5020
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.000 10.000 0.700
p1421[0...n] Speed setpoint filter 2 type / n_set_filt 2 typ
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: 5020
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0 2 0
p1421[0...n] Velocity setpoint filter 2 type / n_set_filt 2 typ
SERVO (Lin) Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: 5020
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0 2 0
p1422[0...n] Speed setpoint filter 2 time constant / n_set_filt 2 T
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5020
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.00 [ms] 5000.00 [ms] 0.00 [ms]