The following sources are available for the displayed setpoint:
- setpoint at the ramp-function generator input (r1119).
- speed setpoint 1 (p1155).
- speed setpoint 2 (p1160).
- speed setpoint for the speed pre-control (p1430).
- setpoint from DSC (for DSC active).
- setpoint via PC (for master control active, p3983).
Dependency: Refer to: r1119, p1155, p1160, p1430
Description: Displays the sum of all velocity setpoints that are present.
The following sources are available for the displayed setpoint:
- setpoint at the ramp-function generator input (r1119).
- velocity setpoint 1 (p1155).
- velocity setpoint 2 (p1160).
- velocity setpoint for the velocity pre-control (p1430).
- setpoint from DSC (for DSC active).
- setpoint via PC (for master control active, p3983).
Dependency: Refer to: r1119, p1155, p1160, p1430
Description: Displays the actual, smoothed actual speed for speed control.
Description: Sets the smoothing time for the actual speed of the speed controller for sensorless closed-loop speed control.
Note: The smoothing must be increased if there is gear backlash. For longer smoothing times, the integral time of the
speed controller must also be increased (e.g. using p0340 = 4).
r1444 Velocity controller, velocity setpoint, total / v_ctrl v_set stat
SERVO (Lin) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 5030
P-Group: Closed-loop control Units group: 4_1 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
- [m/min] - [m/min] - [m/min]
r1445 CO: Actual speed, smoothed / n_ist smooth
VECTOR (n/M) Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: 6040
P-Group: Closed-loop control Units group: 3_1 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
- [RPM] - [RPM] - [RPM]
p1452[0...n] Speed controller speed actual value smoothing time (SLVC) / n_C n_act T_s SLVC
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6040
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.00 [ms] 32000.00 [ms] 10.00 [ms]