Siemens SINAMICS S Series - p1472[0...n] Speed controller sensorless operation integral time; n_ctrl SLVC Tn; p1472[0...n] Velocity controller sensorless operation integral time; v_ctrl SLVC Tn; p1476[0...n] BI: Speed controller hold integrator; n_ctrl integ stop; p1476[0...n] BI: Velocity controller, hold integrator; v_ctrl integ stop

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-412
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Set the integral time for sensorless operation for the speed controller.
Description: Set the integral time for sensorless operation for the velocity controller.
Description: Sets the signal source to hold the integrator for the speed controller.
Description: Sets the signal source to hold the integrator for the velocity controller.
Description: Sets the signal source to set the integrator setting value (p1478).
Dependency: Refer to: p1478, p1479
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1472[0...n] Speed controller sensorless operation integral time / n_ctrl SLVC Tn
SERVO, VECTOR
(n/M)
Can be changed: U, T Calculated: CALC_MOD_CON Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5210
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.0 [ms] 100000.0 [ms] 20.0 [ms]
p1472[0...n] Velocity controller sensorless operation integral time / v_ctrl SLVC Tn
SERVO (Lin) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5210
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.0 [ms] 100000.0 [ms] 20.0 [ms]
p1476[0...n] BI: Speed controller hold integrator / n_ctrl integ stop
SERVO, VECTOR
(n/M)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2520, 5040,
5042, 5210, 6040
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 0
p1476[0...n] BI: Velocity controller, hold integrator / v_ctrl integ stop
SERVO (Lin) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2520, 5040,
5042, 5210
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 0
p1477[0...n] BI: Speed controller set integrator value / n_ctrl integ set
SERVO, VECTOR
(n/M)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2520, 5040,
5042, 5210, 6040
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 0