Parameters
List of parameters
1-412
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Set the integral time for sensorless operation for the speed controller.
Description: Set the integral time for sensorless operation for the velocity controller.
Description: Sets the signal source to hold the integrator for the speed controller.
Description: Sets the signal source to hold the integrator for the velocity controller.
Description: Sets the signal source to set the integrator setting value (p1478).
Dependency: Refer to: p1478, p1479
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1472[0...n] Speed controller sensorless operation integral time / n_ctrl SLVC Tn
SERVO, VECTOR
(n/M)
Can be changed: U, T Calculated: CALC_MOD_CON Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5210
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.0 [ms] 100000.0 [ms] 20.0 [ms]
p1472[0...n] Velocity controller sensorless operation integral time / v_ctrl SLVC Tn
SERVO (Lin) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5210
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.0 [ms] 100000.0 [ms] 20.0 [ms]
p1476[0...n] BI: Speed controller hold integrator / n_ctrl integ stop
SERVO, VECTOR
(n/M)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2520, 5040,
5042, 5210, 6040
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 0
p1476[0...n] BI: Velocity controller, hold integrator / v_ctrl integ stop
SERVO (Lin) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2520, 5040,
5042, 5210
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 0
p1477[0...n] BI: Speed controller set integrator value / n_ctrl integ set
SERVO, VECTOR
(n/M)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2520, 5040,
5042, 5210, 6040
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 0