Parameters
List of parameters
1-442
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the signal source to activate/de-activate the "travel to fixed stop" function
1: Travel to fixed stop is active
0: Travel to fixed stop is inactive
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: When traveling to fixed stop, the fault F07900 "motor blocked" is suppressed.
When the function module "position positioner" (r0108.4 = 1) is activated, this binector input is interconnected as
follows as standard:
BI: p1545 = r2683.14
Description: Sets the speed threshold for the motoring/regenerating limit.
For speeds where the absolute value is less than p1546, then the following applies:
- For p1400.13 = 0: Motoring limit (speed threshold is compared to the speed actual value).
- For p1400.13 = 1: Regenerative limiting (speed threshold is compared to the speed setpoint).
Description: Sets the velocity threshold for the motoring/regenerating limit.
For velocities where the absolute value is less than p1546, then the following applies:
- For p1400.13 = 0: Motoring limit (velocity threshold is compared to the velocity actual value).
- For p1400.13 = 1: Regenerative limiting (velocity threshold is compared to the velocity setpoint).
Description: Displays the torque limit to limit the speed controller output.
Index: [0] = Upper limit
[1] = Lower limit
p1545[0...n] BI: Activates travel to a fixed stop / TfS activation
VECTOR (n/M) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2520, 3617
P-Group: Commands Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 0
p1546 Speed threshold motoring/regenerating / n_thresh mot/regen
SERVO Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [RPM] 210000.0 [RPM] 20.0 [RPM]
p1546 Velocity threshold motoring/regenerating / v_thresh mot/regen
SERVO (Lin) Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [m/min] 1000.0 [m/min] 0.2 [m/min]
r1547[0...1] CO: Torque limit for speed controller output / M_max outp n_ctrl
VECTOR (n/M) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: 7_1 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
- [Nm] - [Nm] - [Nm]