SINAMICS S List Manual (LH1), 07/2007
Description: Sets the proportional gain of the flux controller.
Note: The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameter (p0340 = 4), this value is re-calculated.
Description: Sets the integral time of the flux controller.
Note: For synchronous motors, this parameters has no effect.
The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameter (p0340 = 4), this value is re-calculated.
Description: Sets the integral time of the flux controller.
Note: The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameter (p0340 = 4), this value is re-calculated.
Description: Displays the output of the field weakening controller (synchronous motor) or the output of the flux controller (sepa-
rately-excited synchronous motor, induction motor).
Index: [0] = PI output
[1] = I output
p1590[0...n] Flux controller P gain / Flux controller Kp
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6723
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
0.0 999999.0 10.0
p1592[0...n] Flux controller integral.action time / Flux controller Tn
SERVO Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5722
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 30 [ms]
p1592[0...n] Flux controller integral.action time / Flux controller Tn
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6723
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 30 [ms]
r1593[0...1] CO: Field weakening controller / flux controller output / Field/Fl_ctrl outp
VECTOR (n/M) Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: 6723, 6724,
6726
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]