Parameters
List of parameters
1-458
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the stator current in the q axis after current actual value tracking.
Description: Sets the signal source for the excitation current actual value
Description: Displays the excitation current actual value that is read-in.
Dependency: Refer to: p0390
Description: Sets the minimum excitation current. This means that negative excitation currents can be avoided.
Description: Sets the gain factor for the minimum excitation current, closed-loop control. This is active if the excitation current is
below 75% of p1642.
Dependency: Refer to: p1642
r1639 CO: Current model Isq after actual value tracking / I_mod Isq track
VECTOR (n/M) Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: 6727
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p1640[0...n] CI: Excitation current actual value / I_exc_act val
VECTOR (n/M) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 6727
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
- - 0
r1641 Excitation current actual value / I_exc_act val
VECTOR (n/M) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 6727, 6497
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p1642[0...n] Minimum excitation current / Min I_exc
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
0.1 [%] 50.0 [%] 5.0 [%]
p1643[0...n] Gain factor, minimum excitation current closed-loop control / Min I_exc Kp
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
0.00 5.00 0.40