Description: Sets the valve lockout time to compensate for phase W.
Note: For type PM340 power units, the parameter is limited to 3.98 µs.
Description: Above the current level, the dead time - resulting from the converter switching delays - is compensated by a previ-
ously calculated, constant value . If the relevant phase current setpoint falls below the absolute value defined by
p1832, the corrective value for this phase is continuously reduced.
Dependency: The factor setting of p1832 is automatically set to 0.02 * rated drive converter current (r0207).
If the actual operating frequency exceeds the value of p1831, then p1832 is not applied!
Description: Display for the configuration of the gating unit driver.
Description: Configuration of the actual value correction
p1830 Compensation valve lockout time phase W / Comp t_lock ph W
VECTOR Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 1000000.00 [µs] 0.00 [µs]
p1832 Dead time compensation current level / t_dead_comp I_lev
VECTOR Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [Arms] 10000.0 [Arms] 0.0 [Arms]
r1837 Gating unit configuration / Gating unit config
VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Modulation depth for a flying restart Limited Not limited -
01 Modulation depth for Vdc closed-loop con-
trol
Limited Not limited -
02 Vdc_min controller Active Not active -
03 Motor data identification routine Active Not active -
04 Current offset calculation Active Not active -
05 Simulation oper Active Not active -
06 Direction reversal output phases Active Not active -
07 Direction reversal (including speed encoder) Active Not active -
08 Synchronization (bypass) Active Not active -
p1840[0...n] Actual value correction configuration / AVC config
VECTOR Can be changed: T Calculated: CALC_MOD_ALL Access level: 3
Data type: Unsigned16 Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0000 bin