Parameters
List of parameters
1-592
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Notice: For p0322 = 0, the following applies: p2162 <= 0.1 * p0311
For p0322 > 0, the following applies: p1082 + p2162 <= 1.02 * p0322
If one of the conditions is violated, p2162 is appropriately and automatically reduced when exiting the commission-
ing mode.
Note: For a negative velocity limit (r1087) the hysteresis is effective below the limit value and for a positive velocity limit
(r1084) above the limit value.
Description: Sets the speed threshold value for the "speed setpoint - actual value deviation in tolerance t_off" signal/message
(BO: r2197.7).
Dependency: Refer to: p2164, p2166, r2197
Description: Sets the velocity threshold value for the "speed setpoint - actual value deviation in tolerance t_off" signal/message
(BO: r2197.7).
Dependency: Refer to: p2164, p2166, r2197
Description: Sets the hysteresis speed (bandwidth) for the "speed setpoint - actual value deviation in tolerance t_off" signal/mes-
sage (BO: r2197.7).
Dependency: Refer to: p2163, p2166, r2197
Description: Sets the hysteresis velocity (bandwidth) for the "speed setpoint - actual value deviation in tolerance t_off" sig-
nal/message (BO: r2197.7).
p2163[0...n] Speed threshold 4 / n_thresh val 4
SERVO, VECTOR Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [RPM] 210000.00 [RPM] 90.00 [RPM]
p2163[0...n] Velocity threshold value 4 / v_thresh val 4
SERVO (Lin) Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [m/min] 1000.00 [m/min] 0.90 [m/min]
p2164[0...n] Hysteresis speed 4 / n_hysteresis 4
SERVO, VECTOR Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [RPM] 200.00 [RPM] 2.00 [RPM]
p2164[0...n] Hysteresis velocity 4 / v_hysteresis 4
SERVO (Lin) Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [m/min] 10.00 [m/min] 0.02 [m/min]