Parameters
List of parameters
1-602
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the power-down delay time for the negated signal "run-up completed".
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency: Refer to: p2174, p2194
Description: Sets the power-down delay time for the negated signal "run-up completed".
The message "force setpoint < p2174" (BO: r2198.10) and "force utilization < p2194" (BO: r2199.11) are only eval-
uated after the run-up and the delay time has expired.
Dependency: Refer to: p2174, p2194
Description: Displays the first status word for monitoring functions.
Note: Re bit 01, 02:
The threshold value is set in p2155 and the hysteresis in p2140.
Re bit 03:
The hysteresis is set in p2150.
Re bit 06:
The hysteresis is set in p2162.
Re bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
p2195[0...n] Torque utilization switch-off delay / M_util t_off
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 800.0 [ms]
p2195[0...n] Force utilization switch-off delay / F_util t_off
SERVO (Lin) Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 800.0 [ms]
r2197.1...7 CO/BO: Status word monitoring 1 / ZSW monitor 1
SERVO, VECTOR Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2534
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 |n_act| <= speed threshold value 2 Yes No 8010
02 |n_act| > speed threshold value 2 Yes No 8010
03 n_act >= 0 Yes No 8010
06 |n_act| > n_max Yes No 8010
07 Speed setp - act val deviation in tolerance
t_off
Yes No 8010