Siemens SINAMICS S Series - r3402 Infeed internal status; INF status int; r3402 Infeed status internal BIC; INF status int; r3405.0...7 CO;BO: Status word infeed; INF ZSW

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-700
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the internal status of the infeed module.
Values: 0: Initialization
1: Fault
2: No ON command
3: Offset measurement running
4: ON delay active
5: Precharg. running
6: Pulse enable missing
7: Synchronization running
8: Voltage ramp-up active
9: Operation
10: Shutdown running
11: Identification running
Description: Displays the internal status of the infeed module.
Values: 0: Initialization
1: Fault
2: No ON command
3: Offset measurement running
4: ON delay active
5: Precharg. running
6: Operation
Description: Displays the status word of the infeed.
r3402 Infeed internal status / INF status int
A_INF, S_INF Can be changed: - Calculated: - Access level: 2
Data type: Integer16 Dynamic index: - Func. diagram: 8832, 8932
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 11 -
r3402 Infeed status internal BIC / INF status int
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Integer16 Dynamic index: - Func. diagram: 8932
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 6 -
r3405.0...7 CO/BO: Status word infeed / INF ZSW
A_INF, S_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 8828, 8928
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Smart mode active Yes No -
01 Vdc-ctrl active Yes No -
02 Phase failure detected Yes No -
03 Current limit reached Yes No -
04 Infeed operates regenerating/motoring Regenerative mode Motor mode -
05 Motor operation inhibited Yes No -
06 Regenerative operation inhibited Yes No -
07 DC link undervoltage alarm threshold fallen
below
Yes No -