Parameters
List of parameters
1-700
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the internal status of the infeed module.
Values: 0: Initialization
1: Fault
2: No ON command
3: Offset measurement running
4: ON delay active
5: Precharg. running
6: Pulse enable missing
7: Synchronization running
8: Voltage ramp-up active
9: Operation
10: Shutdown running
11: Identification running
Description: Displays the internal status of the infeed module.
Values: 0: Initialization
1: Fault
2: No ON command
3: Offset measurement running
4: ON delay active
5: Precharg. running
6: Operation
Description: Displays the status word of the infeed.
r3402 Infeed internal status / INF status int
A_INF, S_INF Can be changed: - Calculated: - Access level: 2
Data type: Integer16 Dynamic index: - Func. diagram: 8832, 8932
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 11 -
r3402 Infeed status internal BIC / INF status int
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Integer16 Dynamic index: - Func. diagram: 8932
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 6 -
r3405.0...7 CO/BO: Status word infeed / INF ZSW
A_INF, S_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 8828, 8928
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Smart mode active Yes No -
01 Vdc-ctrl active Yes No -
02 Phase failure detected Yes No -
03 Current limit reached Yes No -
04 Infeed operates regenerating/motoring Regenerative mode Motor mode -
05 Motor operation inhibited Yes No -
06 Regenerative operation inhibited Yes No -
07 DC link undervoltage alarm threshold fallen
below
Yes No -