List of parameters
Parameters
1-771
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: Refer to: r0980, r0981, r0989
Description: Displays the ramp-up state.
Values: 0: Not active
1: Fatal fault
10: Fault
20: Reset all parameters
30: Drive object modified
40: Download using commissioning software
90: Reset Control Unit and delete drive objects
100: Start initialization
110: Instantiate Control Unit basis
150: Wait until actual topology determined
160: Evaluate topology
170: Instantiate Control Unit rest
180: Initialization YDB configuration information
200: First commissioning
210: Create drive packages
250: Wait for topology acknowledge
325: Wait for input of drive type
350: Determine drive type
360: Write into topology-dependent parameters
370: Wait until p0009 = 0 is set
380: Check topology
550: Call conversion functions for parameter
625: Wait non-cyclic starting DRIVE-CLiQ
650: Start cyclic operation
660: Evaluate drive commissioning status
670: Autom. FW update DRIVE-CLiQ components
680: Wait for CU link slaves
690: Wait non-cyclic starting DRIVE-CLiQ
700: Save parameters
725: Wait until DRIVE-CLiQ cyclic
740: Check the ability to operate
750: Interrupt enable
800: Initialization finished
Description: Displays whether writing to parameters is inhibited.
r3996 = 0: Write to parameter is not inhibited.
0 < r3996 < 100: Write to parameter is inhibited. The value shows how the calculations are progressing.
r3988 Ramp-up state / Ramp-up state
CU_CX32, CU_S Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 800 -
r3996 Parameter write inhibit status / Par_write inhib st
A_INF, B_INF,
CU_CX32, CU_LINK,
CU_S, DMC20,
SERVO, S_INF,
TB30, TM15,
TM15DI_DO, TM17,
TM31, TM41, VEC-
TOR
Can be changed: - Calculated: - Access level: 1
Data type: Unsigned8 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -