Siemens SINAMICS S Series - p0099[0...5] Device target topology; Device_target topo; p0100 IEC;NEMA mot stds; IEC;NEMA mot stds

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-82
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note: Topology coding: abcd efgh hex
a = number of Active Line Modules
b = number of Motor Modules
c = number of motors
d = number of encoders (or the line supply voltage sensing for Active Line Modules)
e = number of additional encoders (or the line supply voltage sensing for Active Line Modules)
f = number of Terminal Modules
g = number of terminal boards
h = reserved
if the value 0 is displayed in all indices, then components are not detected via DRIVE-CLiQ.
If a value F hex occurs at a position of the coding (abcd efgh hex), then an overflow has occurred.
Description: Sets the device target topology in coded form (refer to r0098). The setting is made during commissioning.
Index: [0] = DRIVE-CLiQ socket X100
[1] = DRIVE-CLiQ socket X101
[2] = DRIVE-CLiQ socket X102
[3] = DRIVE-CLiQ socket X103
[4] = DRIVE-CLiQ socket X104
[5] = DRIVE-CLiQ socket X105
Dependency: The parameter can only be written into for p0097 = 0.
To perform an automatic device configuration run, an index of the device target topology must be set to the value of
the device actual topology in r0098 for acknowledgement. An index of the device actual topology with a value other
than 0 must be selected.
Refer to: p0097, r0098
Refer to: A01330
Note: The parameter can only be set to the values 0, the value of the actual device topology, the value of the actual
device target topology and FFFFFFFF hex.
If the value 0 is displayed in all of the indices, then the system has still not be commissioned.
The value FFFFFFFF hex indicates that the topology was not generated by the automatic device configuration but
was commissioned using the commissioning software (e.g. using parameter download).
Description: Defines whether the motor and drive converter power settings (e.g. rated motor power - p0307) are expressed in
[kW] or [hp].
Depending on the selection, the rated motor frequency (p0310) is either set to 50 Hz or 60 Hz.
The following applies for IEC drives: The power factor (p0308) should be parameterized.
The following applies for NEMA drives: The efficiency (p0309) should be parameterized.
Values: 0: IEC-Motor (50 Hz, SI units)
1: NEMA motor (60 Hz, US units)
Dependency: If p0100 is changed, all of the rated motor parameters are reset. Only then are possible unit changeovers made.
p0099[0...5] Device target topology / Device_target topo
CU_CX32, CU_S Can be changed: C1(1) Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: - Func. diagram: -
P-Group: Topology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
p0100 IEC/NEMA mot stds / IEC/NEMA mot stds
SERVO, VECTOR Can be changed: C2(1) Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: FEM Expert list: 1
Min Max Factory setting
0 1 0