Parameters
List of parameters
1-860
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Values: 0: Inactive
1: Save SMI data
2: Download SMI data
11: SMI data for the selected component not found on CF
12: Component with the selected component number not available.
13: CompactFlash card does not have sufficient memory space
14: Incorrect format of the saved data
15: Data not able to be downloaded into SMI
Dependency: Refer to: p4690, p4692
Note: SMI: SINAMICS Sensor Module Integrated
Help for error value = 11:
Save the data for the originally existing SMI on the CompactFlash card.
Help for error value = 12:
Set the correct component number.
Help for error value = 13:
Use a CompactFlash card with a larger memory.
Help for error value = 15:
Use an SMI card that is empty.
Description: Setting to save data of all existing Sensor Module Integrated (SMI) on the CompactFlash card.
Values: 0: Inactive
1: Save data from all SMI on CompactFlash card
13: CompactFlash card does not have sufficient memory space
Dependency: Refer to: p4690, p4691
Note: SMI: SINAMICS Sensor Module Integrated
p4692 is automatically set to 0 at the end of the data save procedure.
The procedure must be repeated if the data save operation was interrupted (e.g. if the power supply voltage failed).
Values: 0: Stop trace
1: Start trace
Index: [0] = Trace 0
[1] = Trace 1
p4692 Save SMI data of all SMI / Save SMI data
CU_CX32, CU_S Can be changed: T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 13 0
p4700[0...1] Trace control / Trace control
CU_CX32, CU_S Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Expert list: 0
Min Max Factory setting
0 1 0