Siemens SINAMICS S Series - p4692 Save SMI data of all SMI; Save SMI data; p4700[0...1] Trace control; Trace control

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-860
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Values: 0: Inactive
1: Save SMI data
2: Download SMI data
11: SMI data for the selected component not found on CF
12: Component with the selected component number not available.
13: CompactFlash card does not have sufficient memory space
14: Incorrect format of the saved data
15: Data not able to be downloaded into SMI
Dependency: Refer to: p4690, p4692
Note: SMI: SINAMICS Sensor Module Integrated
Help for error value = 11:
Save the data for the originally existing SMI on the CompactFlash card.
Help for error value = 12:
Set the correct component number.
Help for error value = 13:
Use a CompactFlash card with a larger memory.
Help for error value = 15:
Use an SMI card that is empty.
Description: Setting to save data of all existing Sensor Module Integrated (SMI) on the CompactFlash card.
Values: 0: Inactive
1: Save data from all SMI on CompactFlash card
13: CompactFlash card does not have sufficient memory space
Dependency: Refer to: p4690, p4691
Note: SMI: SINAMICS Sensor Module Integrated
p4692 is automatically set to 0 at the end of the data save procedure.
The procedure must be repeated if the data save operation was interrupted (e.g. if the power supply voltage failed).
Values: 0: Stop trace
1: Start trace
Index: [0] = Trace 0
[1] = Trace 1
p4692 Save SMI data of all SMI / Save SMI data
CU_CX32, CU_S Can be changed: T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 13 0
p4700[0...1] Trace control / Trace control
CU_CX32, CU_S Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Expert list: 0
Min Max Factory setting
0 1 0