Parameters
List of parameters
1-902
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the rated power of the individual power units connected in parallel for various load duty cycles.
The sum of the rated powers of all power units connected in parallel is displayed in r0206.
Index: [0] = Rating plate
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 continuous duty cycle
[4] = S6 load duty cycle
Dependency: The value is displayed in [kW] or [hp].
Refer to: p0100, p0205
Description: Displays the rated current of the individual power units connected in parallel for various load duty cycles.
The sum of the rated currents of all power units connected in parallel is displayed in r0207.
Index: [0] = Rating plate
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 continuous duty cycle
[4] = S6 load duty cycle
Dependency: Refer to: p0205
Description: Displays the maximum output current of the individual power units connected in parallel.
The sum of the maximum currents of all power units connected in parallel is displayed in r0209.
Index: [0] = Rating plate
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 continuous duty cycle
[4] = S6 load duty cycle
Dependency: Refer to: p0205
r7250[0...4] Par_circuit power unit rated power / PU P_rated
A_INF (Parallel),
B_INF (Parallel),
S_INF (Parallel),
VECTOR (Parallel)
Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Converter Units group: 14_6 Unit selection: p0100
Not for motor type: - Expert list: 1
Min Max Factory setting
- [kW] - [kW] - [kW]
r7251[0...4] Par_circuit power unit rated current / PU PI_rated
A_INF (Parallel),
B_INF (Parallel),
S_INF (Parallel),
VECTOR (Parallel)
Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r7252[0...4] Par_circuit maximum power unit current / PU I_max
A_INF (Parallel),
B_INF (Parallel),
S_INF (Parallel),
VECTOR (Parallel)
Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]