375/528
The possible continuous braking power P
rated-Brake
and the peak braking power P
max-Brake
are included in the following
table of unit-specific technical data. They refer to the upper response thresholds, i.e. to V
DC-max
= 774 V at line supply
voltages of 380 V to 480 V and to V
DC-max
= 1158 V at line supply voltages of 500 V to 690 V. For other response
thresholds, the braking power must be reduced in proportion to V
DC-Brake
.
The table below states the key technical data for SINAMICS S120 Motor Modules in their application as 3-phase
Braking Modules.
S120 Motor Modules
in
standard application
S120 Motor Modules in application as 3-phase Braking Modules
Output
power
at 400 V
or 690 V
[ kW ]
Rated
output
current
I
rated
[ A ]
Continuous
braking
current
I
rated-Brake
[ A ]
Base
load
braking
current
I
L-Brake
[ A ]
Base
load
braking
current
I
H-Brake
[ A ]
Maximum
braking
current
I
max-Brake
[ A ]
Upper
response
threshold
V
DC-max
[ V ]
Continuous
braking
power
(upper
response
threshold)
P
rated-Brake
[ kW ]
Peak braking
power
(upper
response
threshold)
P
max-Brake
[ kW ]
Minimum
braking
resistance
(cold state)
R
BR-min
[ ]
380 V – 480 V 3AC or 510 V – 720 V DC
110 210 210 205 178 307 774 197 288 1.02
132 260 255 245 229 368 774 239 345 0.85
160 310 290 283 259 424 774 272 398 0.74
200 380 340 331 304 497 774 319 466 0.63
250 490 450 438 402 657 774 422 617 0.48
315 605 545 531 414 797 774 511 748 0.39
400 745 680 662 520 993 774 638 932 0.32
450 840 800 781 667 1171 774 751 1099 0.27
560 985 900 877 786 1316 774 845 1235 0.24
710 1260 1215 1186 1087 1779 774 1140 1669 0.18
800 1405 1365 1331 1221 1996 774 1281 1873 0.16
500 V – 690 V 3AC or 675 V – 1035 V DC
75 85 85 80 76 120 1158 119 168 3.90
90 100 100 95 89 142 1158 140 199 3.30
110 120 115 110 103 165 1158 161 232 2.84
132 150 144 136 129 204 1158 202 286 2.29
160 175 175 171 157 255 1158 246 358 1.84
200 215 215 208 192 312 1158 302 438 1.50
250 260 255 245 229 368 1158 358 517 1.27
315 330 290 281 246 422 1158 407 592 1.11
400 410 400 390 358 585 1158 562 821 0.80
450 465 450 437 403 656 1158 632 921 0.71
560 575 515 502 460 752 1158 723 1056 0.62
710 735 680 657 608 985 1158 955 1383 0.48
800 810 805 785 720 1178 1158 1130 1654 0.40
900 910 905 875 810 1313 1158 1271 1843 0.36
1000 1025 1020 995 913 1493 1158 1432 2096 0.31
1200 1270 1230 1191 1002 1787 1158 1727 2509 0.26
1500 1560 in preparation
Technical data of S120 Motor Modules in their application as 3-phase Braking Modules
Dimensioning of the braking resistors
The formula below defines the required limits of the resistance values R
BR
of the three star-connected braking
resistors. Allowance for the increase in resistance as a function of load (up to 30 %) must be included in the
calculation:
R
BR-min
< R
BR
< R
BR-max
.