EasyManua.ls Logo

Siemens SINAMICS S120 - Page 678

Siemens SINAMICS S120
826 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cabinet design and EMC Booksize
12.4 Arrangement of components and equipment
Booksize Power Units
678 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Table 12- 3 Comparison of the connection versions
Var.
Module width
[mm]
Installa-
tion
Current-
carrying
capacity of
the
DC-link bus-
bar [A]
DC-link
adapter
6SL3162-...
DC-link
busbar
Fastening of the
DC-link adapter
to two DC-link
busbars
Screws
Washers
1
50 … 100
Right
≤ 100
2BM01-0AA0
Standard
2 screws
M4x20
No
2 50 … 100 Right ≤ 150
2BM10-0AA0
Reinforced
2 screws M4x20 No
3
50 … 100
Left
≤ 100
2BM01-0AA0
Standard
2 screws
M4x16
No
4
150
Right
≤ 150
2BM01-0AA0
Standard
2 screws
M4x20
No
5
150 … 300
Left
≤ 150
2BM01-0AA0
Standard
2 screws
M4x20
Yes
6
200 … 300
Right
≤ 200
2BM01-0AA0
Standard
4 screws
M4x20
No
Connections as cross-sectional drawings (view from below)
Note
The different connection versions of the DC
-link adapter are shown in the following cross-
sec
tional drawings. Special features are highlighted in bold in the table above.
Variant 1: Module width 50-100 mm, connected to the drive line-up from the right, standard DC-link
busbar
DC-link adapter 6SL3162-2BM01-0AA0 (4 hole)
Standard DC-link busbar (4 mm)
Connecting the DC-link adapter to the module using 2 M4x20 screws
Connecting the DC-link busbar to the module using 2 M4x16 screws
DC-link bridge
Figure 12-6 Variant 1 (representation from below)