SINAMICS Engineering Manual – November 2015
Ó Siemens AG
356/528
The DRIVE-CLiQ cable [2] can be brought into a Motor Module in frame size FX through the side panel only if the
adjacent Motor Module in frame size GX is mounted at a distance of Z > about 20 mm.
DRIVE-CLiQ connections on Motor Modules of different frame sizes
If the distance Z is less than about 20 mm, i.e. the Motor Modules are mounted flush with one another, the DRIVE-
CLiQ cable must be brought into the Chassis unit from below, as illustrated by cable 3 in the picture.
If the drive system is supplied by a Basic Line Module or a Smart Line Module, the DRIVE-CLiQ connections must be
made analogous to systems supplied by the Active Line Module. The Control Unit is latched into the fixing lugs on the
left-hand side of the Line Module. The DRIVE-CLiQ cables from the Control Unit to the Line Module and to the first
Motor Module must be routed through the rubber sleeve on the left-hand side panel of the unit.