SINAMICS S120 Cabinet Modules
Engineering Information
SINAMICS Engineering Manual – November 2015
Ó Siemens AG
394/528
Active Line Modules + Active Interface Modules
Active Infeeds must be regarded as requiring two separate auxiliary voltage supplies, i.e. one for the Active Interface
Module (AIM) and one for the Active Line Module (ALM).
The AIM requires the following voltages:
24 V DC: Control electronics
230 V AC: Cabinet ventilation, control voltage of precharging contactors depending on frame size
The ALM requires the following voltages:
24 V DC: Control electronics
400 V resp. 690 V AC: Power unit fans
Active Interface Modules and Active Line Modules are delivered due to the required power connections as one unit.
For this reason, the auxiliary voltage connections of the AIM are already made to the auxiliary voltage supply system
of the ALM in the delivery state. Fuse protection down-circuit of the auxiliary voltage supply system is provided in the
Cabinet Modules.
The power requirement in the table below is based on the combination of Active Interface Module and Active Line
Module.
Order No.
Frame
size
Rated rectifier/
regenerative
power at 400 V
or 690 V
Rated rectifier/
regenerative
current
I
rated
Current requirement
1)
24 V
DC
230 V AC 400 V or 690V AC
50 Hz 60 Hz 50 Hz 60 Hz
[kW] [A] [A] [A] [A] [A] [A]
Supply voltage 380 V – 480 V 3AC (DC link voltage 570 V – 720 V)
6SL3730-7TE32-1BA3 FX+FI 132 210 1.27 0.6 0.9 0.63 0.9
6SL3730-7TE32-6BA3 FX+FI 160 260 1.27 0.6 0.9 1.13 1.6
6SL3730-7TE33-8BA3 GX+GI 235 380 1.52 1.2 1.8 1.8 2.7
6SL3730-7TE35-0BA3 GX+GI 300 490 1.52 1.2 1.8 1.8 2.7
6SL3730-7TE36-1BA3 HX+HI 380 605 1.57 4.6 6.8 3.6 5.4
6SL3730-7TE38-4BA3 HX+HI 500 840 1.57 4.6 6.8 3.6 5.4
6SL3730-7TE41-0BA3 JX+JI 630 985 1.67 4.9 7.3 5.4 8.0
6SL3730-7TE41-0BC3 JX+JI 630 985 1.67 4.9 7.3 5.4 8.0
6SL3730-7TE41-4BA3 JX+JI 900 1405 1.67 4.9 7.3 5.4 8.0
6SL3730-7TE41-4BC3 JX+JI 900 1405 1.67 4.9 7.3 5.4 8.0
Supply voltage 500 V – 690 V 3AC (DC link voltage 750 V – 1035 V)
6SL3730-7TG35-8BA3 HX+HI 630 575 1.57 4.6 6.8 2.1 3.1
6SL3730-7TG37-4BA3 JX+JI 800 735 1.67 4.9 7.3 3.1 4.6
6SL3730-7TG37-4BC3 JX+JI 800 735 1.67 4.9 7.3 3.1 4.6
6SL3730-7TG41-0BA3 JX+JI 1100 1025 1.87 4.9 7.3 3.1 4.6
6SL3730-7TG41-0BC3 JX+JI 1100 1025 1.87 4.9 7.3 3.1 4.6
6SL3730-7TG41-3BA3 JX+JI 1400 1270 1.87 4.9 7.3 3.1 4.6
6SL3730-7TG41-3BC3 JX+JI 1400 1270 1.87 4.9 7.3 3.1 4.6
1)
Power requirement of control electronics, auxiliary power supply for fans.