Commissioning
5.3 Procedure for commissioning via STARTER
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
131
Configure the infeed
Figure 5-15 Configure the infeed
8. Choose whether the line and DC link identification function is to be activated during initial
start-up.
(Recommendation: "Activate identification" = "Yes")
9. Specify the Device connection voltage.
10. Click Continue >.