Operation
6.6 PROFIBUS
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
213
Bit Meaning Explanation BICO
1 No alarm present
15 Alarm, drive converter thermal
overload
0 Alarm, drive converter thermal overload
The overtemperature alarm for the converter is active.
BO: r2135.15
Status word 1 (interface mode PROFIdrive VIK-NAMUR, p2038 = 2)
Table 6-16 Status word 1 (interface mode PROFIdrive VIK-NAMUR, p2038 = 2)
Bit Meaning Explanation BICO
1 Ready to power up
Power supply on, electronics initialized, line contactor
released if necessary, pulses inhibited.
0 Ready to power up
0 Not ready to power up
BO: r0899.0
1 Ready
Voltage at Line Module (i.e. line contactor closed (if used)),
field being built up.
1 Ready
0 Not ready
Cause: No ON command has been issued.
BO: r0899.1
1 Operation enabled
Enable electronics and pulses, then ramp up to active
setpoint.
2 Operation enabled
0 Operation inhibited
BO: r0899.2
1 Fault active
The drive is faulty and is, therefore, out of service. The drive
switches to Power-on inhibit once the fault has been
acknowledged and the cause has been remedied.
The active faults are stored in the fault buffer.
3 Fault active
0 No fault present
There is no active fault in the fault buffer.
BO: r2139.3
1 No OFF2 active 4 No OFF2 active /
coasting active (OFF2)
0 Coasting active (OFF2)
An OFF2 command is present.
BO: r0899.4
1 No OFF3 active 5 0 = Fast stop active (OFF3)
0 Coasting active (OFF3)
An OFF3 command is present.
BO: r0899.5
1 Power-on disable
A restart is only possible through OFF1 followed by ON.
6 Power-on disable
0 No power-up inhibit
Power-up is possible.
BO: r0899.6
7 Alarm present 1 Alarm present
The drive is operational again. No acknowledgement
necessary.
The active alarms are stored in the alarm buffer.
BO: r2139.7