Procedure
1. Assemble the X1 plug to the converter.
2. Attach the cable terminals to the plug as shown below:
Figure6-3 Connecting to the single-phase mains supply network
Figure6-4 Connecting to the three-phase mains supply network
More information
For more information about cable req
uirements, see Section "Cables and connectors
(Page124)".
For more information about assembling cable terminals, see Section "Assembling cables
(Page734)".
6.4.3 Using several single-phase converters in machines and plants
Overview
Evaluate the input currents of single-phase converters in your machine or plant in terms of
harmonics and unbalance.
Description
In unfavorable cases, the harmonic currents of several converters in the neutral conductor (N)
add up to a value greater than the currents of the line conductors (L1, L2, L3). The current-
carrying capacity of the neutral conductor must be sucient for this.
Connecting
6.4Connecting the mains supply
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA 127