10.4 Gain switching
Overview
The function of gain switc
hing is used to switch between two sets of scaling factors.
With the gain switching function, you can implement the following operations:
Increase the gains during servo lock and decrease gains to reduce noise during rotation.
Increase the gains during settling to shorten the stop settling time.
Ensure the stability of the servo system when the load inertia moment ratio varies greatly
during a stop.
Note
Se
t the scaling factors accor
ding to the following formulas to obtain expected servo gains:
Position loop gain = p29178*p29110 (fast PTI mode)
Speed loop gain = p1460*p29120
Speed loop integral time = p1462/p29121
Requirement
Do not use the function in the t
orque control mode.
Disable the functions of autotuning.
Description of function
The function of gain switching is disabled by default (p29130 = 0), and only scaling factor 1 is
valid in this case.
Tuning
10.4Gain switching
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
302 Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA