Table 11-5 Message classes and coding of various diagnostic interfaces
Text of the message class Number ac‐
cor
ding to
PROFIdriv
e
Diagnostics inter‐
face
Cause and remedy PN
(hex)
DS1
(dec)
Hardware/sof
tware fault
A hardware or softw
are malfunction was detected.
• Carry out a POWER ON for the relevant component.
• If it occurs again, contact the hotline.
• Replace device.
(1) 9000 0
Line fault
A line supply fault has occurred (phase failure, v
oltage level...).
• Check the line supply/fuses.
• Check the supply voltage.
• Check the wiring.
(2) 9001 1
Supply voltage fault
An electronics supply
voltage fault (48 V, 24 V, 5 V…) was detec‐
ted.
• Check the wiring.
• Check the voltage level.
(3) 9002 2
DC link overvoltage
The DC link voltage has assumed an inadmis
sibly high value.
• Check the dimensioning of the system (line supply, reactor,
voltages).
• Check the infeed settings.
(4) 9003 3
Power electronics fault
An inadmissible operating stat
e of the power electronics has
been identied (overcurrent, overtemperature, IGBT failure…).
• Check that the permissible duty cycles are complied with.
• Check the ambient temperatures (fan).
(5) 9004 4
Electronic component overload
The temperature in t
he component has exceeded the highest
permissible limit.
• Check the ambient temperature /control cabinet cooling.
(6) 9005 5
Ground fault/inter-phase short-circuit detected
A ground fault/int
erphase short-circuit was detected in the power
cables or in the motor windings.
• Check the power cables (connection).
• Check the motor.
(7) 9006 6
Motor overload
The motor was operat
ed outside the permissible limits (temper‐
ature, current, torque…).
• Check the duty cycles and set limits.
• Check the ambient temperature/motor cooling.
(8) 9007 7
System messages
11.3Faults and alarms
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
324 Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA