Requirement
You have an SD card with the appropriate rmware, or you have an empty SD card with a
maximum capacity of 32GB onto which you can load the rmware.
You can download the available rmware versions at the following link (https://
support.industry.siemens.com/cs/ww/en/ps/29596/dl).
Procedure
Proceed as follo
ws to update the rmware using an SD card:
1. Switch o the converter.
2. Insert the SD card into the converter and switch on the converter.
The new rmware is installed. This process takes approximately two minutes.
RDY COM Explanation of LED displays
Firmware update is active:
• Do not switch o the po
wer supply.
• Do not disconnect the motor from the converter.
- Firmware update is completed
3. Switch the converter o and remove the SD car
d.
4. Switch on the converter again. Check whether the new version is installed. The rmware
version of the converter is displayed on the home page of the web server.
More information
You can nd more information about the SD card in Section "AUTOHOTSPOT".
12.1.3 Replacing the converter
Overview
You may only replace a converter with another converter if certain requirements are adhered to.
Corrective maintenance
12.1Service and maintenance for the converter
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
484 Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA