Dependency: See also: p0613
See also: F07011, A07012
NOTICE
After the drive is switched on, the system starts to determine the motor temperature with an assumed model value. This
means t
hat the value for t
he motor utilization is only valid after a stabilization time.
r0036[0...2] Power unit overload
Data type: FloatingPoint32 Visible in: Extended display
R
ead permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Parame
ter group: Mode signals / displays, Power unit
Unit: %
Description: Display when the power unit is overloaded.
A reference value is
de󹪝ned for the monitoring functions.
An overload (0 %) is not displayed if the reference value is not exceeded.
The display value increases if the reference value is exceeded.
An alarm is output if an overload is active over a certain time period; a fault is output when 100% is reached.
Index: [0] = I2t (AC)
[1] = Reserved
[2] = Reserved
Dependency
: See also: p0290
See also: F30005, A30256, A30257, F30258, A30267, F30268
Note
For index [0]:
This index show
s the actual state of the I2t monitoring on the AC side.
The reference value represents the AC current that the power unit can permanently provide, without the in󹪞uence of
switching losses (e.g. the continuously permissible current of capacitors, inductances, busbars, etc.).
For index [1]:
This index shows the actual state of the active power monitoring.
The reference value represents the active power that the power unit can continuously provide.
For index [2]:
This index shows the actual state of the I2t monitoring on the DC side.
The reference value represents the DC current that can continuously 󹪞ow in the DC link.
r0037[0...10] Power unit temperatures
Data type: FloatingPoint32 Visible in: Extended display
R
ead permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or drive applications
Parame
ter group: Mode signals / displays, Power unit
Unit: °C
Description: Display for the temperatures in the power unit.
Appendix
A.3Parameters
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
592 Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA