A.4.1.2 Assembling the encoder connector
Overview
The Siemens IX-C connector is used for encoder connection to the converter. It consists of the
following components:
① Shielding A ④ Front cover
② Back cover ⑤ Insulation-displacement contact (IDC) terminal
③ Shielding B
FigureA-1 IX-C connector
Requirement
Y
ou have prepar
ed appropriate tools, a raw cable, and the Siemens IX-C connector.
Procedure
1. Prepare the cable.
– Remove the outer sheath of the cable by 17 mm.
– Remove the cable shield by 12 mm.
– Fold the remaining cable shield backward over the cable sheath, and wrap the folded
cable shield with copper tape.
2. Arrange the conductors as shown below.
Appendix
A.4Assembling cables
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2