See also
DRIVE-CLiQ interface (Page 48)
LEDs of the Power Stack Adapters (Page 89)
Analog and digital outputs and temperature sensor connections
Table 3-3 Power Stack Adapter 4: Analog and digital outputs and temperature sensor connections
Terminal X331
1
X332
2
X333
3
1 M AO 7- I_IN 3
2 DO 7 AO 7+ TEMP 3-
3 DO 6 AO 6+ TEMP 3+
4 M AO 6- I_OUT 3
5 M AO 5- I_IN 2
6 DO 5 AO 5+ TEMP 2-
7 DO 4 AO 4+ TEMP 2+
8 M AO 4- I_OUT 2
9 M AO 3- I_IN 1
10 DO 3 AO 3+ TEMP 1-
11 DO 2 AO 2+ TEMP 1+
12 M AO 2- I_OUT 1
13 M AO 1- I_IN 0
14 DO 1 AO 1+ TEMP 0-
15 DO 0 AO 0+ TEMP 0+
16 M AO 0- I_OUT 0
Max. connectable cross-section 1.5 mm²; type: Screw terminal
1
Technical data for X331:
● Max. output voltage: Infeed voltage at X310.3 minus approx. 2 V
● Max. load current per output: 200 mA, continuously short-circuit-proof
● Output delay:
– For "0" to "1": Typ. 100 μs for 0.2 A resist. load
– For "1" to "0": Typ. 10 μs for 0.2 A resist. load
2
Technical data for X332:
● Voltage range: -10 to 10 V, continuously short-circuit-proof
● Max. load current per output: 3 mA
● Resolution: 12-bit
3
Technical data for X333:
Pt100 temperature sensors use the four wire measurement principle. For a two-wire
measurement, you must jumper terminal I_OUT n with TEMP n+, and TEMP n- with I_IN n.
Description
3.4 Components
SINAMICS SM120 6SL38855?B
Operating Instructions 12/2015 37