Detailed information about cabling of the drive is provided in the circuit diagrams supplied.
Please ensure that the maximum cable lengths between the drive and motor are not
exceeded.
Make sure that the permissible cable capacitance is not exceeded.
Use appropriate screws for the cable lugs provided.
The tightening torque for the M12 screws is 50 Nm.
Clean the contact surfaces before screwing the connections.
Apply a thin layer of grease to the screws.
Table 6-2 Cleaning agents and grease
Materials required
Cleaning agent Ethyl alcohol
Grease 2G from Elektrolube
NOTICE
Thermal destruction
Cables that have not been properly secured at the connection point, represent a high electrical
transition resistance, which can result in thermal destruction.
Tighten the screws with the specified torques. Tighten the M12 screws with a torque of 50
Nm.
Electrical connection
6.7 Connecting power cables
SINAMICS SM120 6SL38855?B
Operating Instructions 12/2015 81