Commissioning
4.3 Quick commissioning
SINAMICS V20 Inverter
36 Getting Started, 07/2012, A5E03728127
Parameter Description Factory
default
Default for
Cn003
Remarks
P1022[0] BI: Fixed frequency selection bit 2 722.5 722.3 DI4
P1001[0] Fixed frequency 1 10 10 Speed low
P1002[0] Fixed frequency 2 15 15 Speed middle
P1003[0] Fixed frequency 3 25 25 Speed high
P0771[0] CI: Analog output 21 21 Actual frequency
P0731[0] BI: Function of digital output 1 52.3 52.2 Inverter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Inverter fault active
Connection macro Cn004 - Fixed speeds in binary mode
Fixed speeds with ON command in binary mode
Up to 16 different fixed frequency values (0 Hz, P1001 ... P1015) can be selected by the
fixed frequency selectors (P1020 ... P1023)
OK
OK
M
M
10V AI1 AI2 0V DI1 DI2 DI3 DI4 DIC 24V 0V
AO + AO- DO1 + DO1- P + N-
DO2
0V 0V
0~20mA=
0~50 /60 Hz
220V
N
)L[HGVSHHGELW
)L[HGVSHHGELW
)L[HGVSHHGELW
)L[HGVSHHGELW
)DXOW5XQQLQJ6SHHG

   



Connection macro settings:
Parameter Description Factory
default
Default for
Cn004
Remarks
P0700[0] Selection of command source 1 2 Terminals as command source
P1000[0] Selection of frequency 1 3 Fixed frequency
P0701[0] Function of digital input 1 0 15 Fixed speed bit 0
P0702[0] Function of digital input 2 0 16 Fixed speed bit 1
P0703[0] Function of digital input 3 9 17 Fixed speed bit 2
P0704[0] Function of digital input 4 15 18 Fixed speed bit 3
P1016[0] Fixed frequency mode 1 2 Binary mode
P0840[0] BI: ON / OFF1 19.0 1025.0 Inverter starts at the fixed speed
selected