Commissioning
4.3 Quick commissioning
SINAMICS V20 Inverter
38 Getting Started, 07/2012, A5E03728127
Connection macro settings:
Parameter Description Factory
default
Default for
Cn005
Remarks
P0700[0] Selection of command source 1 2 Terminals as command source
P1000[0] Selection of frequency 1 23 Fixed frequency + analog setpoint
P0701[0] Function of digital input 1 0 1 ON / OFF
P0702[0] Function of digital input 2 0 15 Fixed speed bit 0
P0703[0] Function of digital input 3 9 16 Fixed speed bit 1
P0704[0] Function of digital input 4 15 9 Fault acknowledgement
P1016[0] Fixed frequency mode 1 1 Direct selection mode
P1020[0] BI: Fixed frequency selection bit 0 722.3 722.1 DI2
P1021[0] BI: Fixed frequency selection bit 1 722.4 722.2 DI3
P1001[0] Fixed frequency 1 10 10 Fixed speed 1
P1002[0] Fixed frequency 2 15 15 Fixed speed 2
P1074[0] BI: Disable additional setpoint 0 1025.0 FF disables the additional setpoint
P0771[0] CI: Analog output 21 21 Actual frequency
P0731[0] BI: Function of digital output 1 52.3 52.2 Inverter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Inverter fault active