Commissioning
4.3 Quick commissioning
SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127
39
Connection macro Cn006 - External push button control
Note that the command sources are pulse signals.
OK
OK
M
M
10V AI1 AI2 0V DI1 DI2 DI3 DI4 DIC 24V 0V
AO + AO- DO1 + DO1- P + N-
DO2
0V 0V
0~20mA=
0~50 /60 Hz
220V
N
2))KROG
21SXOVH
023XS
023GRZQ
)DXOW5XQQLQJ6SHHG

   



Connection macro settings:
Parameter Description Factory
default
Default for
Cn006
Remarks
P0700[0] Selection of command source 1 2 Terminals as command source
P1000[0] Selection of frequency 1 1 BOP MOP
P0701[0] Function of digital input 1 0 2 OFF1 / hold
P0702[0] Function of digital input 2 0 1 ON pulse
P0703[0] Function of digital input 3 9 13 MOP up pulse
P0704[0] Function of digital input 4 15 14 MOP down pulse
P0727[0] Selection of 2 / 3-wire method 0 3 3-wire
ON pulse + OFF1 / HOLD +
Reverse
P0771[0] CI: Analog output 21 21 Actual frequency
P0731[0] BI: Function of digital output 1 52.3 52.2 Inverter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Inverter fault active
P1040[0] Setpoint of the MOP 5 0 Initial frequency
P1047[0] MOP ramp-up time of the RFG 10 10 Ramp-up time from zero to
maximum frequency
P1048[0] MOP ramp-down time of the RFG 10 10 Ramp-down time from maximum
frequency to zero