Commissioning
4.3 Quick commissioning
SINAMICS V20 Inverter
40 Getting Started, 07/2012, A5E03728127
Connection macro Cn007 - External push buttons with analog control
Note that the command sources are pulse signals.
OK
10V AI1 AI2 0V DI1 DI2 DI3 DI4 DIC 24V 0V
AO + AO- DO1 + DO1- P + N-
DO2
0V 0V
0~20mA=
0~50 /60 Hz
220V
0~10 V=
0~50/60Hz
N
2))KROG
)RUZDUGSXOVH21
5HYHUVHSXOVH21
)DXOWDFNQRZOHGJHPHQWSXOVH
)DXOW5XQQLQJ6SHHG
2))
)RUZDUG
5HYHUVH
Connection macro settings:
Parameter Description Factory
default
Default for
Cn007
Remarks
P0700[0] Selection of command source 1 2 Terminals as command source
P1000[0] Selection of frequency 1 2 Analog
P0701[0] Function of digital input 1 0 1 OFF hold
P0702[0] Function of digital input 2 0 2 Forward pulse + ON
P0703[0] Function of digital input 3 9 12 Reverse pulse + ON
P0704[0] Function of digital input 4 15 9 Fault acknowledgement
P0727[0] Selection of 2 / 3-wire method 0 2 3-wire
STOP + Forward pulse + Reverse
pulse
P0771[0] CI: Analog output 21 21 Actual frequency
P0731[0] BI: Function of digital output 1 52.3 52.2 Inverter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Inverter fault active