Commissioning
4.4 Restoring to defaults
SINAMICS V20 Inverter
48 Getting Started, 07/2012, A5E03728127
Parameter Access
level
Function Text menu
(if P8553 = 1)
P1003[0] 2 Fixed frequency setpoint 3
(FIX F3)
P2201[0] 2 Fixed PID frequency setpoint 1
(PID F1)
P2202[0] 2 Fixed PID frequency setpoint 2
(PID F2)
P2203[0] 2 Fixed PID frequency setpoint 3
(PID F3)
4.4 Restoring to defaults
Restoring to factory defaults
Parameter Function Setting
P0003 User access level = 1 (standard user access level)
P0010 Commissioning parameter = 30 (factory setting)
P0970 Factory reset = 21: parameter reset to factory defaults deleting user defaults if
stored
Restoring to user defaults
Parameter Function Setting
P0003 User access level = 1 (standard user access level)
P0010 Commissioning parameter = 30 (factory setting)
P0970 Factory reset = 1: parameter reset to user defaults if stored, else factory
defaults
After the setting for P0970, the inverter displays "8 8 8 8 8" and then the screen shows
"P0970". P0970 and P0010 are automatically reset to their original value 0.