SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127
49
Parameter list
5
Parameter Description Range Factory default Acc. level
r0002 Inverter state - - 2
P0003 User access level 0 - 4 1 1
0 User defined parameter list
1 Standard
2 Extended
3 Expert
4 Service
P0004 Parameter filter 0 - 22 0 1
0 All parameters 12 Inverter features
2 Inverter 13 Motor control
3 Motor 19 Motor identification
5 Technology application / units 20 Communication
7 Commands, binary I/O 21 Warnings / faults / monitoring
8 Analog input and analog output 22 Technology controller
10 Setpoint channel / RFG
P0010 Commissioning parameter 0 - 30 0 1
0 Ready
1 Quick commissioning
2 Inverter
29 Download
30 Factory setting
r0018 Firmware version - - 1
r0021 CO: Actual filtered frequency [Hz] - - 2
r0025 CO: Actual output voltage [V] - - 2
r0026[0] CO: Actual filtered DC-link voltage [V] - - 2
r0027 CO: Actual output current [A] - - 2
r0031 CO: Actual filtered torque [Nm] - - 2
r0032 CO: Actual filtered power - - 2
r0035[0...2] CO: Actual motor temperature [°C] - - 2
r0039 CO: Energy consumpt. meter [kWh] - - 2
P0040 Reset energy consumpt. and energy saved meter 0 - 1 0 2
0 No reset
1 Reset r0039 to 0
P0042[0...1] Energy saving scaling 0.000 - 100.00 0.000 2
Index: [0] Factor for kWh to currency conversion
[1] Factor for kWh to CO2 conversion