Parameter list
SINAMICS V20 Inverter
50 Getting Started, 07/2012, A5E03728127
Parameter Description Range Factory default Acc. level
r0043[0...2] Energy saved [kWh] - - 2
r0050 CO / BO: Active command data set - - 2
r0051[0...1] CO: Active inverter data set (DDS) - - 2
r0052.0...15 CO / BO: Active status word 1 - - 2
r0053.0...15 CO / BO: Active status word 2 - - 2
P0100 Europe / North America 0 - 2 0 1
0 Europe [kW], motor base frequency is 50 Hz
1 North America [hp], motor base frequency is 60 Hz
2 North America [kW], motor base frequency is 60 Hz
r0206 Rated inverter power [kW] / [hp] - - 2
r0207[0...2] Rated inverter current [A] - - 2
r0208 Rated inverter voltage [V] - - 2
r0209 Maximum inverter current [A] - - 2
P0304[0...2] Rated motor voltage [V] 10 - 2000 400 1
P0305[0...2] Rated motor current [A] 0.01 - 10000.00 1.86 1
P0307[0...2] Rated motor power 0.01 - 2000.00 0.75 1
P0308[0...2] Rated motor cosφ 0.000 - 1.000 0.000 1
P0309[0...2] Rated motor efficiency [%] 0.0 - 99.9 0.0 1
P0310[0...2] Rated motor frequency [Hz] 12.00 - 599.00 50.00 1
P0311[0...2] Rated motor speed [RPM] 0 - 40000 1395 1
P0335[0...2] Motor cooling 0 - 3 0 2
0 Self-cooled: Shaft mounted fan attached motor (IC410 or IC411)
1 Force-cooled: Separately powered cooling fan (IC416)
2 Self-cooled and internal fan
3 Force-cooled and internal fan
P0340[0...2] Calculation of motor parameters 0 - 4 0 2
0 No calculation
1 Complete parameterization
2 Calculation of equivalent circuit data
3 Calculation of V/f control data
4 Calculation of controller settings only
P0507 Application macro 0 - 255 0 1
r0512 CO: Scaled filtered frequency - - 2
P0604[0...2] Threshold motor temperature [°C] 0.0 - 200.0 130.0 2
P0640[0...2] Motor overload factor [%] 10.0 - 400.0 150.0 2
P0700[0...2] Selection of command source 0 - 5 1 1
0 Factory default setting
1 Operator panel (keypad)
2 Terminal
5 USS / MBUS on RS485
P0701[0...2] Function of digital input 1 0 - 99 0 2
0 Digital input disabled 16 Fixed frequency selector bit1