Parameter list
SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127
57
Parameter Description Range Factory default Acc. level
0 Disable
1 Fault
2 Warn
P2361[0...2] Cavitation threshold [%] 0.00 - 200.00 40.00 2
P2362[0...2] Cavitation protection time [s] 0 - 65000 30 2
P2365[0...2] Hibernation enable / disable 0 - 1 0 2
0 Disabled
1 Enabled
P2940 BI: Release wobble function - 0.0 2
P2945 Wobble signal frequency [Hz] 0.001 - 10.000 1.000 2
P2946 Wobble signal amplitude [%] 0.000 - 0.200 0.000 2
P2947 Wobble signal decrement step 0.000 - 1.000 0.000 2
P2948 Wobble signal increment step 0.000 - 1.000 0.000 2
P2949 Wobble signal pulse width [%] 0 - 100 50 2
r2955 CO: Wobble signal output [%] - - 2
r3113.0...15 CO / BO: Fault bit array - - 1
P3350[0...2] Super torque mode 0 - 3 0 2
0 Super torque modes disabled
1 Super torque enabled
2 Hammer start enabled
3 Blockage clearing enabled
Index: [0] Inverter data set 0 (DDS0)
[1] Inverter data set 1 (DDS1)
[2] Inverter data set 2 (DDS2)
P3351[0...2] BI: Super torque enable - 0 2
P3352[0...2] Super torque startup mode 0 - 2 1 2
0 Enabled on first run after power-up
1 Enabled on every run
2 Enabled by digital input
P3353[0...2] Super torque ramp time [s] 0.0 - 650.0 5.0 2
P3354[0...2] Super torque frequency [Hz] 0.0 - 599.0 5.0 2
P3355[0...2] Super torque boost level [%] 0.0 - 200.0 150.0 2
P3356[0...2] Super torque boost time [s] 0.0 - 20.0 5.0 2
P3357[0...2] Hammer start boost level [%] 0.0 - 200.0 150.0 2
P3358[0...2] Number of hammer cycles 1 - 10 5 2
P3359[0...2] Hammer on time [ms] 0 - 1000 300 2
P3360[0...2] Hammer off Time [ms] 0 - 1000 100 2
P3361[0...2] Blockage clearing frequency [Hz] 0.0 - 599.0 5.0 2
P3362[0...2] Blockage clearing reverse time [s] 0.0 - 20.0 5.0 2
P3363[0...2] Enable rapid ramp 0 - 1 0 2
0 Disable rapid ramp for blockage clearing
1 Enable rapid ramp for blockage clearing