Parameter list
SINAMICS V20 Inverter
58 Getting Started, 07/2012, A5E03728127
Parameter Description Range Factory default Acc. level
P3364[0...2] Number of blockage clearing cycles 1 - 10 1 2
r3365 Status word: super torque - - 2
P3852[0...2] BI: Enable frost protection - 0 2
P3853[0...2] Frost protection frequency [Hz] 0.00 - 599.00 5.00 2
P3854[0...2] Condensation protection current [%] 0 - 250 100 2
P3900 End of quick commissioning 0 - 3 0 1
0 No quick commissioning
1 End quick commissioning with factory reset
2 End quick commissioning
3 End quick commissioning only for motor data
P8553 Menu type 0 - 1 0 1
0 Menus with no text
1 Menus with some text