SINAMICS V20 Inverter
Getting Started, 07/2012, A5E03728127
61
Technical specifications
7
Line supply characteristics
Three phase 400 V inverters
Voltage range 380 ... 480 V AC (tolerance: -15 % ... +10 %)
47 ... 63 Hz
Current derating at high input voltages:
2XWSXWFXUUHQW>@
9ROWDJH9
 










Overvoltage category EN 60664-1 Category III
Permissible supply
configuration
TN, TT, IT
1)
, TT earthed line
Supply environment Second environment (private power network)
1)
Note that only unfiltered inverters can be operated on IT power system.
Overload capability
Average output current 100 % rated
Overload current 150 % rated for 60 seconds
Maximum overload cycle 150 % rated for 60 seconds followed by 94.5 % rated for 540 seconds (average 100 %
rated)