Task navigation
SINAMICS V-ASSISTANT Online Help
Operating Manual, 04/2017, A5E36618042-003
151
Change request above the currently valid limit (example: a parameter value is too large for the drive power)
CC hex
Change request not permitted
(change is not permitted as the access code is not available)
Via FC 16, with one request, up to 122 registers can be written to directly one after the other.
In addition to the slave address, enter the transfer type, the start address and the number of
the following registers in the header.
You control the access in the user data via register 40601.
In register 40602, you define the acyclic access as well as the length of the request data.
Register 40603 contains the request reference, which is defined by the user, and the access
type reading or writing.
From register 40603 and higher, the request aligns acyclic communication via data set 47.
Register 40604 contains the number of the drive object (for V90 always 2) and the number of
parameters that are read out or written to.
Register 40605 contains the attribute (for V90 always 0x10). In the number of elements you
specify how many indices are read.
Example: p1215 and p1120 read acyclically
The table below formats a request to read the parameter values of p1215 and p1120 from
slave number 1.
10 h
0258 h
000A h
14 h
1
2,3
4,5
6
Function code (write multiple)
Register start address
Number of registers to be read (40601 … 40610)
Number of data bytes (10 registers, each 2 bytes = 20