Installing and putting a TIM into operation
4.7 Startup activities of the TIM module
Station control system
System Manual, 07/2009, C79000-G8976-C178-07
173
exceptions are the LINK and RX/TX LEDs that have no significance during the startup of the
TIM 3V-IE variants.
LED displays during startup
The following table summarizes the startup phases.
Table 4- 22 LED activity on the TIM 3V-IE variants during the various startup phases
Phase Activity SF RUN STOP KBus TxD RxD
1 Power ON
followed by hardware initialization
On On On On On On
2 Loading the operating system from flash
memory
Off On On On On On
3 Starting VxWorks operating system Off Off On On On On
4 Loading and starting TIM firmware Off Off Off On On On
5 Initializing flash file system and starting
the start manager
Off Flashes On Off Off Off
6 Loading and starting P bus driver Off Flashes On On Off Off
7 Loading and starting subscriber
management (SubA)
Off Flashes On Off On Off
8 Loading and starting LAN-COM Off Flashes On On On Off
9 Loading and starting subscriber
management (MesA)
Off Flashes On Off Off On
10 Loading and starting time-of-day driver Off Flashes On On Off On
11 Loading and starting the TD7 software of
the TIM (TD7onTIM) on the TIM
Off Flashes On Off On On
12 Loading and starting WAN driver Off Flashes On On On On
13a Startup completed without error Off On Off X
1)
X
1)
X
1)
13b Startup completed with error On Off On X
2)
X
2)
X
2)
13c Startup aborted - user parameter
assignment missing Module expects user
parameter assignment
Off Off On Flashes Flashes On
13d Startup aborted -
No firmware loaded.
Off Off On On Flashes Flashes
13e Startup aborted - No SDBs and no
firmware loaded.
Off Off On Flashes Flashes Flashes
13f Default startup completed Off Flashes Flashes On On On
1) The LEDs KBus, TxD and RxD now operate in normal mode
2) The LEDs KBus, TxD and RxD remain in the phase in which the error occurred