Introduction to the SINAUT ST7 system
1.4 The classic SINAUT ST7 modems
Station control system
System Manual, 07/2009, C79000-G8976-C178-07
35
MD2
Terminating resistor can be adjusted
For 1200 and 2400 bps
For 9600 and 19,200 bps
For tapping point
600 ohms
150 ohms
> 6 kilohms
Ready to send
At 1200 bps
At 2400 bps
At 9600 and 19,200 bps
After 7 ms
After 4 ms
After 0.5 ms
Lower / upper keying frequency
At 1200 bps
At 2400 bps
At 9600 and 19,200 bps
1300 Hz / 2100 Hz
2400 Hz / 3300 Hz
20,800 Hz / 33,600 Hz
Asynchronous character format 10 or 11 bits
Floating optical relay output
Max. connected voltage
Max. permitted permanent current
Max. R
on
60 V AC/DC
400 mA
3 ohms
Surge withstand capability
U
1.2/50
to DIN VDE 0804
between supply circuit and
FSK remote line circuits
Optical relay output
2.5 kV
2.5 kV
Compatible with SINAUT modems
MD100
MD124
At 1200 bps
At 1200, 2400 and 19,200 bps
Certifications and approvals EU approval CE 0682 X
Technical specifications of the MD3 analog dial-up modem
MD3
Interfaces
Attachment to telephone network or dedicated
line
RS-232 attachment to DTE
RS-485 attachment to DTE
Connection to power supply
RJ-12
9-pin D-sub male connector
9-pin D-sub female connector
4-pin terminal strip
Power supply 24 V DC
Current consumption
From 24 V DC
200 mA
Power loss 4.8 W